ASTM D3612-96: GC Analysis of Transformer Gas on Carboxen®-1010 PLOT

ASTM D3612-96: GC Analysis of Transformer Gas on Carboxen®-1010 PLOT

Conditions

column Carboxen-1010 PLOT, 30 m x 0.53 mm I.D. (25467)
oven 35 C (8.5 min), 24 C/min to 250 C
carrier gas argon, 3.0 ml/min
sample 9 analytes, each at 500 ppm
injection 10.0 muLdirect using a sample valve, 150 C
inj. temp. 200 C
detector TCD, 230 C, Methanizer, 375 C, and FID, 230 C in series

Description

Categories Analytical Chromatography, GC Applications, Light Hydrocarbons, Gases, Hydrocarbons
Featured Industry Chemicals and Industrial Polymers
Legal Information Carboxen is a registered trademark of Sigma-Aldrich Co. LLC
suitability application for GC

Analyte

  • Acetylene
  • Carbon dioxide
  • Carbon monoxide
  • Ethane
  • Ethylene
  • Hydrogen
  • Methane
  • Nitrogen
  • Oxygen